Configurable 4–20 mA Current Output
The OMRON E5CN-C2MT-500 features a configurable 4–20 mA or 0–20 mA DC control output with a maximum permitted load of 600 Ω, suitable for compatible process control interfaces and current-input devices.
Available to order
Request a QuoteNeed multiple units or help confirming a model? Contact our team.
Shop with confidence. If for any reason you are not satisfied, you can take advantage of our hassle-free return and exchange service within 30 days. The seller covers all shipping costs for returns or exchanges—there are no extra shipping fees for you to pay, ensuring a worry-free shopping experience.
Available payment methods
Ships from 4 U.S. Warehouses – Contact Us for Estimated Delivery Times.
Technical specifications, features, applications and purchasing information.
| Brand | OMRON |
| Model Number | E5CN-C2MT-500 |
| Product Category | Digital Temperature Controller |
| Product Series | E5CN Basic Type |
| Controller Format | 1/16 DIN, Panel-Mounted |
| Front Panel Dimensions | 48 × 48 mm |
| Controller Dimensions (W × H × D) | 48 × 48 × 78 mm, Nominal |
| Recommended Panel Cutout | 45 × 45 mm, +0.6/0 mm Tolerance |
| Case Color | Black |
| Rated Supply Voltage | 100 to 240 VAC |
| Power Supply Frequency | 50/60 Hz |
| Permissible Supply Voltage Range | 85% to 110% of Rated Voltage |
| Maximum Power Consumption | 7.5 VA |
| Sensor Input Type | Universal Thermocouple / Platinum Resistance Thermometer |
| Supported Thermocouples | K, J, T, E, L, U, N, R, S, B, W and PL II |
| Supported RTD Inputs | Pt100 and JPt100 |
| Additional Temperature-Model Inputs | Compatible Infrared Temperature Sensor Signals and 0–50 mV Input; Refer to Input Configuration |
| Control Output 1 | DC Current Output |
| Control Output Current Range | 4–20 mA DC or 0–20 mA DC, Configurable |
| Maximum Current Output Load | 600 Ω |
| Current Output Resolution | Approximately 10,000 Steps |
| Auxiliary Outputs | 2 Relay Outputs |
| Auxiliary Relay Contact Type | SPST-NO |
| Auxiliary Relay Rating | 250 VAC, 3 A Resistive Load |
| Control Methods | ON/OFF or 2-PID with Auto-Tuning |
| Temperature Sampling Period | 250 ms |
| Display | Dual 4-Digit, 11-Segment PV/SV Display |
| Display Character Height | PV: 11 mm; SV: 6.5 mm |
| Alarm Functions | Configurable Upper-Limit, Lower-Limit, Deviation and Other Supported Alarm Types |
| Optional Expansion | Supports Compatible E53-CN Option Units, Subject to Controller Production Version |
| Communication Interface | RS-485 Available with a Compatible Optional Communication Unit; Not Standard |
| Terminal Cover | Included, -500 Designation |
| Front Panel Protection | IP66 with Correct Waterproof Packing and Installation |
| Rear Case Protection | IP20 |
| Terminal Protection | IP00 |
| Ambient Operating Temperature | -10 to +55°C, Without Icing or Condensation |
| Operating Humidity | 25% to 85% RH |
| Storage Temperature | -25 to +65°C |
| Approximate Controller Weight | 150 g |
| Manufacturer Documentation | OMRON E5CN/E5CN-U Basic-Type Digital Temperature Controller Datasheet; User Manual H156 |
The OMRON E5CN-C2MT-500 features a configurable 4–20 mA or 0–20 mA DC control output with a maximum permitted load of 600 Ω, suitable for compatible process control interfaces and current-input devices.
The controller accepts multiple thermocouple types, including K, J and T, as well as Pt100 and JPt100 resistance temperature detectors. Select the appropriate input type and measurement range during commissioning.
Selectable ON/OFF and 2-PID control methods with auto-tuning support temperature regulation in properly configured heating and cooling processes.
Two SPST-NO auxiliary relay outputs can be assigned to supported alarm and control-related functions. Each is rated 250 VAC at 3 A for a resistive load under the manufacturer's conditions.
The 48 × 48 mm front panel incorporates an 11-segment dual PV/SV display and front-panel programming keys, enabling operators to view process temperature and adjust configuration settings.
The -500 model includes a terminal cover. Compatible optional E53-CN modules can provide additional functions such as RS-485 communication or event inputs, depending on the controller production version and installed option.
We support online purchase of the OMRON E5CN-C2MT-500 Digital Temperature Controller. If you need to make bulk purchases and inquire about other products, please contact our team to inform us of your purchase requirements. We will provide you with information such as quantity quotations, delivery dates, and transportation methods.
What is the OMRON E5CN-C2MT-500?
It is a 1/16 DIN digital temperature controller with universal thermocouple and platinum RTD input, a configurable DC current control output, two auxiliary relay outputs and a 100–240 VAC power supply.
What power supply voltage does this controller require?
The E5CN-C2MT-500 is specified for 100 to 240 VAC at 50/60 Hz. It is not the 24 VAC/VDC version.
Does the controller have a 4–20 mA control output?
Yes. Its primary control output can be configured for 4–20 mA DC or 0–20 mA DC, with a maximum load resistance of 600 Ω.
Is its primary control output a relay or an SSR voltage signal?
Neither. The C designation identifies a DC current control output. Relay-output and SSR-driving voltage-output models use different order codes.
Which temperature sensors are supported?
Supported sensor inputs include K, J, T, E, L, U, N, R, S, B, W and PL II thermocouples, plus Pt100 and JPt100 resistance thermometers. Select the appropriate input setting before use.
Does it accept standard 4–20 mA process signals as a measurement input?
The E5CN-C2MT-500 is the temperature-input version, not the general analog current/voltage input version. The E5CN-C2ML-500 is the corresponding analog-input variant. Do not confuse the current control output with the measurement input type.
How many alarm outputs are included?
It includes two auxiliary relay outputs that can be configured for supported alarm functions, each with an SPST-NO contact rated 250 VAC at 3 A for resistive loads.
Does it support PID control?
Yes. The controller supports 2-PID control with auto-tuning, as well as ON/OFF control.
What are its panel dimensions?
The controller has a 48 × 48 mm front face and an approximately 78 mm nominal depth, with a recommended 45 × 45 mm panel cutout subject to manufacturer tolerances.
Is the front panel waterproof?
The front panel is rated IP66 when the specified waterproof packing is properly installed and maintained. The rear case is IP20 and the terminal section is IP00, so the entire controller is not waterproof.
Does E5CN-C2MT-500 include RS-485 communication?
Not as a standard built-in function. RS-485 communication requires a compatible optional E53-CN communication unit, and option-unit compatibility depends on the controller production version.
What should be checked before ordering?
Confirm exact model E5CN-C2MT-500, 100–240 VAC supply, thermocouple/RTD input type, 4–20 mA or 0–20 mA primary current output, two auxiliary relay outputs, terminal cover, panel dimensions, existing wiring and any required optional communication or event-input modules.