Ultraviolet Flame Detection
The Honeywell C7027A1023 Minipeeper detects ultraviolet radiation emitted by combustion flames and provides a flame detection signal to compatible burner flame safeguard controls.
Available to order
Request a QuoteNeed multiple units or help confirming a model? Contact our team.
Shop with confidence. If for any reason you are not satisfied, you can take advantage of our hassle-free return and exchange service within 30 days. The seller covers all shipping costs for returns or exchanges—there are no extra shipping fees for you to pay, ensuring a worry-free shopping experience.
Available payment methods
Ships from 4 U.S. Warehouses – Contact Us for Estimated Delivery Times.
Technical specifications, features, applications and purchasing information.
| Brand | Honeywell |
| Model Number | C7027A1023 |
| Manufacturer Material Number | C7027A1023/U |
| Product Category | Ultraviolet Flame Detector |
| Product Series | Minipeeper C7027A |
| Flame Detection Method | Ultraviolet Radiation Sensing |
| Compatible Fuel Applications | Gas, Oil and Coal-Fired Burners |
| Lead Wire Length | 8 ft (96 in. / 2438 mm) |
| Electrical Connections | 2 NEC Class 1 Lead Wires |
| Wire Size | 18 AWG |
| Mounting Connection | Integral Collar with 1/2-14 NPSM Internal Threads |
| Sighting Pipe Size | 1/2 in. |
| Overall Dimensions | Approximately 27 mm Diameter × 102 mm Length |
| Ambient Operating Temperature | -18°C to +102°C (0°F to 215°F) |
| Maximum Pressure Rating | 5 psi (34.5 kPa) |
| Maximum Vibration | 0.5 g |
| Operating Duty | Intermittent Flame Supervision; Burner Must Recycle at Least Once Every 24 Hours |
| Ultraviolet Sensing Tube | Not Field Replaceable |
| Compatible Flame Amplifier Families | R7249A/B, R7849A/B, R7749B, R7259 and R7290; Verify Exact Control Compatibility |
| UL Approval | UL Listed, File MP268, Guide MCCZ |
| CSA Approval | CSA Certified, Master Report LR95329-1 |
| Manufacturer Technical Reference | Honeywell Publication 60-2026; Combustion Catalog 70-8911 |
The Honeywell C7027A1023 Minipeeper detects ultraviolet radiation emitted by combustion flames and provides a flame detection signal to compatible burner flame safeguard controls.
The detector is equipped with two NEC Class 1 lead wires measuring approximately 8 feet (2438 mm), supporting electrical connection to an appropriate flame safeguard control circuit.
An integral collar with 1/2-14 NPSM internal threads allows mounting on a compatible 1/2-inch flame sighting pipe. The compact body measures approximately 27 mm in diameter and 102 mm in length.
Honeywell specifies the C7027A1023 for gas-fired, oil-fired and coal-fired burners when used with a properly matched ultraviolet flame amplifier and flame safeguard control.
The model is rated for ambient temperatures from -18°C to +102°C. The manufacturer also specifies a maximum pressure rating of 5 psi when the detector is correctly installed.
The Minipeeper detector is intended for intermittent burner operation and integration with compatible Honeywell flame safeguard equipment. The complete burner safety sequence must follow the manufacturer's requirements.
We support online purchase of the Honeywell C7027A1023 Ultraviolet Flame Detector. If you need to make bulk purchases and inquire about other products, please contact our team to inform us of your purchase requirements. We will provide you with information such as quantity quotations, delivery dates, and transportation methods.
What is the Honeywell C7027A1023?
It is a Honeywell Minipeeper ultraviolet flame detector used with compatible burner flame safeguard controls for combustion flame supervision.
What type of flame does C7027A1023 detect?
The detector senses ultraviolet radiation emitted by combustion flames. Honeywell identifies applications involving gas-fired, oil-fired and coal-fired burners.
How long are the detector lead wires?
The C7027A1023 includes two lead wires measuring 8 feet (96 inches or approximately 2438 mm).
What is the operating temperature range?
The specified ambient operating temperature range is -18°C to +102°C (0°F to 215°F).
What mounting connection does this detector use?
It uses an integral collar with 1/2-14 NPSM internal threads for installation on a compatible 1/2-inch sighting pipe.
What are its physical dimensions?
The manufacturer drawing indicates an overall length of approximately 102 mm and a diameter of approximately 27 mm.
What is the maximum pressure rating?
Honeywell specifies a maximum pressure rating of 5 psi (34.5 kPa) when the detector is correctly installed.
Which Honeywell flame amplifiers can be used?
The Honeywell combustion catalog lists amplifier families including R7249A/B, R7849A/B, R7749B, R7259 and R7290. The complete flame safeguard control and amplifier combination must be verified before installation.
Can this detector be used for continuous burner operation?
The C7027A Minipeeper is intended for intermittent operation. Honeywell requires the burner to recycle at least once every 24 hours. Continuous-operation systems require an appropriately specified detector and flame safeguard arrangement.
Can its ultraviolet sensing tube be replaced in the field?
No. Honeywell specifies that the C7027A ultraviolet sensing tube is not field replaceable.
Can C7027A1031 replace C7027A1023?
Do not assume direct interchangeability. The variants have different published ambient temperature specifications. Confirm the complete model, flame amplifier compatibility, wiring, mounting and burner safety requirements.
What should be checked before ordering?
Confirm model C7027A1023, manufacturer material number C7027A1023/U, 8-foot lead wires, 1/2-inch sighting pipe connection, -18°C to +102°C ambient rating, compatible flame safeguard control, burner duty cycle and the required installation conditions.
Send us your part number and technical requirements.