Skip to content
Honeywell

Honeywell C7027A1023 Ultraviolet Flame Sensor Detector for Burner Control

PRODUCT PRICE USD
$83.18

Available to order

Stock: 200
Request a Quote

Need multiple units or help confirming a model? Contact our team.

Shop with confidence

30-Day Risk-Free Returns & Exchanges

Shop with confidence. If for any reason you are not satisfied, you can take advantage of our hassle-free return and exchange service within 30 days. The seller covers all shipping costs for returns or exchanges—there are no extra shipping fees for you to pay, ensuring a worry-free shopping experience.

View Our Return Policy

Payments

Available payment methods

  • PayPal
  • Bank transfer

Service Guarantee

Shipping

Free standard shipping within the U.S

Shipping details

Estimated delivery

Ships from 4 U.S. Warehouses – Contact Us for Estimated Delivery Times.

Delivery details

Enjoy greater discounts on bulk orders

Please contact our team for bulk purchases

Contact our team
Honeywell C7027A1023 Ultraviolet Flame Sensor Detector for Burner Control
PRODUCT DOCUMENTATION

Product Information

Technical specifications, features, applications and purchasing information.

Technical Specifications

Brand Honeywell
Model Number C7027A1023
Manufacturer Material Number C7027A1023/U
Product Category Ultraviolet Flame Detector
Product Series Minipeeper C7027A
Flame Detection Method Ultraviolet Radiation Sensing
Compatible Fuel Applications Gas, Oil and Coal-Fired Burners
Lead Wire Length 8 ft (96 in. / 2438 mm)
Electrical Connections 2 NEC Class 1 Lead Wires
Wire Size 18 AWG
Mounting Connection Integral Collar with 1/2-14 NPSM Internal Threads
Sighting Pipe Size 1/2 in.
Overall Dimensions Approximately 27 mm Diameter × 102 mm Length
Ambient Operating Temperature -18°C to +102°C (0°F to 215°F)
Maximum Pressure Rating 5 psi (34.5 kPa)
Maximum Vibration 0.5 g
Operating Duty Intermittent Flame Supervision; Burner Must Recycle at Least Once Every 24 Hours
Ultraviolet Sensing Tube Not Field Replaceable
Compatible Flame Amplifier Families R7249A/B, R7849A/B, R7749B, R7259 and R7290; Verify Exact Control Compatibility
UL Approval UL Listed, File MP268, Guide MCCZ
CSA Approval CSA Certified, Master Report LR95329-1
Manufacturer Technical Reference Honeywell Publication 60-2026; Combustion Catalog 70-8911

Key Features

Ultraviolet Flame Detection

The Honeywell C7027A1023 Minipeeper detects ultraviolet radiation emitted by combustion flames and provides a flame detection signal to compatible burner flame safeguard controls.

8-Foot Prewired Connection

The detector is equipped with two NEC Class 1 lead wires measuring approximately 8 feet (2438 mm), supporting electrical connection to an appropriate flame safeguard control circuit.

Compact Sighting Pipe Mounting

An integral collar with 1/2-14 NPSM internal threads allows mounting on a compatible 1/2-inch flame sighting pipe. The compact body measures approximately 27 mm in diameter and 102 mm in length.

Gas, Oil and Coal Burner Applications

Honeywell specifies the C7027A1023 for gas-fired, oil-fired and coal-fired burners when used with a properly matched ultraviolet flame amplifier and flame safeguard control.

Industrial Temperature Capability

The model is rated for ambient temperatures from -18°C to +102°C. The manufacturer also specifies a maximum pressure rating of 5 psi when the detector is correctly installed.

Burner Flame Supervision

The Minipeeper detector is intended for intermittent burner operation and integration with compatible Honeywell flame safeguard equipment. The complete burner safety sequence must follow the manufacturer's requirements.

Applications

  • Industrial gas burner flame monitoring
  • Oil-fired burner flame detection
  • Coal-fired combustion equipment
  • Commercial boiler burner supervision
  • Industrial furnace flame safeguard systems
  • Process heating combustion control
  • Burner management system maintenance
  • Compatible Honeywell Minipeeper detector replacement

Purchase Information

We support online purchase of the Honeywell C7027A1023 Ultraviolet Flame Detector. If you need to make bulk purchases and inquire about other products, please contact our team to inform us of your purchase requirements. We will provide you with information such as quantity quotations, delivery dates, and transportation methods.

Frequently Asked Questions

What is the Honeywell C7027A1023?
It is a Honeywell Minipeeper ultraviolet flame detector used with compatible burner flame safeguard controls for combustion flame supervision.


What type of flame does C7027A1023 detect?
The detector senses ultraviolet radiation emitted by combustion flames. Honeywell identifies applications involving gas-fired, oil-fired and coal-fired burners.


How long are the detector lead wires?
The C7027A1023 includes two lead wires measuring 8 feet (96 inches or approximately 2438 mm).


What is the operating temperature range?
The specified ambient operating temperature range is -18°C to +102°C (0°F to 215°F).


What mounting connection does this detector use?
It uses an integral collar with 1/2-14 NPSM internal threads for installation on a compatible 1/2-inch sighting pipe.


What are its physical dimensions?
The manufacturer drawing indicates an overall length of approximately 102 mm and a diameter of approximately 27 mm.


What is the maximum pressure rating?
Honeywell specifies a maximum pressure rating of 5 psi (34.5 kPa) when the detector is correctly installed.


Which Honeywell flame amplifiers can be used?
The Honeywell combustion catalog lists amplifier families including R7249A/B, R7849A/B, R7749B, R7259 and R7290. The complete flame safeguard control and amplifier combination must be verified before installation.


Can this detector be used for continuous burner operation?
The C7027A Minipeeper is intended for intermittent operation. Honeywell requires the burner to recycle at least once every 24 hours. Continuous-operation systems require an appropriately specified detector and flame safeguard arrangement.


Can its ultraviolet sensing tube be replaced in the field?
No. Honeywell specifies that the C7027A ultraviolet sensing tube is not field replaceable.


Can C7027A1031 replace C7027A1023?
Do not assume direct interchangeability. The variants have different published ambient temperature specifications. Confirm the complete model, flame amplifier compatibility, wiring, mounting and burner safety requirements.


What should be checked before ordering?
Confirm model C7027A1023, manufacturer material number C7027A1023/U, 8-foot lead wires, 1/2-inch sighting pipe connection, -18°C to +102°C ambient rating, compatible flame safeguard control, burner duty cycle and the required installation conditions.

?
Need help confirming a model?

Send us your part number and technical requirements.

Contact Our Team