6 RTD Input Channels
Provides six channels for direct connection of RTD temperature sensors without external signal conditioning.
Available to order
Request a QuoteNeed multiple units or help confirming a model? Contact our team.
Shop with confidence. If for any reason you are not satisfied, you can take advantage of our hassle-free return and exchange service within 30 days. The seller covers all shipping costs for returns or exchanges—there are no extra shipping fees for you to pay, ensuring a worry-free shopping experience.
Available payment methods
Ships from 4 U.S. Warehouses – Contact Us for Estimated Delivery Times.
Technical specifications, features, applications and purchasing information.
| Brand | Fanuc |
| Model Number | HE693RTD600 |
| Product Category | RTD Input Module |
| Number of Channels | 6 |
| Supported RTD Types | PT-90, PT-100E, PT-100C, PT-100Z, Ni-120, Cu-10, Cu-50, Cu-53, Cu-100, Pt-1000, TD5R, Linear Resistance |
| Resolution | 0.5°C / 0.5°F |
| Accuracy | ±0.5°C typical ( ±1.0°C for Cu-10 and TD5R) |
| Input Impedance | >1000 MΩ |
| Power Consumption | 75 mA @ 5 VDC |
| Update Time | 50 channels per second |
| Operating Temperature | 0°C to 60°C |
Provides six channels for direct connection of RTD temperature sensors without external signal conditioning.
Supports PT-90, PT-100 variants, Ni-120, Cu-10, Cu-50, Cu-53, Cu-100, Pt-1000, TD5R, and linear resistance sensors.
Delivers temperature values in 0.5°C or 0.5°F increments for precise monitoring.
Input impedance greater than 1000 MΩ ensures minimal loading on RTD sensors.
Consumes 75 mA at 5 VDC from the PLC backplane.
We support online purchase of the Fanuc HE693RTD600 RTD Input Module. If you need to make bulk purchases and inquire about other products, please contact our team to inform us of your purchase requirements. We will provide you with information such as quantity quotations, delivery dates, and transportation methods.
What is the HE693RTD600? The HE693RTD600 is a 6-channel RTD input module for GE Fanuc Series 90-30 PLC systems.
How many RTD channels does it have? It has six RTD input channels.
What RTD types are supported? It supports PT-90, PT-100 variants, Ni-120, Cu-10, Cu-50, Cu-53, Cu-100, Pt-1000, TD5R, and linear resistance sensors.
What is the resolution? The resolution is 0.5°C or 0.5°F.
What is the accuracy? Typical accuracy is ±0.5°C, with ±1.0°C for Cu-10 and TD5R sensors.
What is the power consumption? It consumes 75 mA at 5 VDC.
What is the operating temperature range? The operating temperature range is 0°C to 60°C.
Does it require external signal conditioning? No, all analog and digital processing is performed on the module.